UPS list

Uninterruptible Power Supplies at the experiment:

 

RackTables OBJECT NAME LOCATION           MODEL                                   BATTERY TYPE LAST BATTERY  CHANGE  DEVICES POWERED                    NOTES
             
UPS12
(not in Rack Tables)
Control Room
Slow Controls Terminals, floor
APC SMT1500C

(Smart-UPS 1500)
 RBC7 9/2022 (original battery) sc3.starp.bnl.gov (TBD)

2 LCDs for sc3 (TBD)
Serial #: 3S2138X17984
Manuf date: Sept. 2021
Bought April 2022

black tower

IP: 130.199.60.146

BNL tag: A111249
UPS7 Control Room, Slow Controls Terminals, floor near south west corner APC SMT1500NC  RBC7 6/2017 (original battery)

sc5.starp.bnl.gov

2 LCDs for sc5

speakers for sc5

Serial #: AS1711333192
Manuf. date: March 2017

black tower

has an AP9631 network interface with an environmental monitor probe (ups7.starp.bnl.gov)

IP: 130.199.60.181

BNL tag: A76077

  Control Room, north of Slow Controls Terminals, floor APC BR1000G

(Back-UPS Pro 1000)
 RBC123

12/2017

08/2021

sc.starp.bnl.gov

alh.starp.bnl.gov + 2 LCDs

Serial #: 3B1204X18919
Manuf. date: January 2012
bought summer 2012

black "tower"

BNL tag: A073737

self-test can be initiated from the front panel by pressing and holding the power button for 6 seconds.  (Caution - pressing and holding the power button for two seconds (one beep) and releasing it will shutdown the UPS!  For the self-test, keep pressing until the 2nd beep!)

  Control Room, TPC Terminals, console shelf

 APC SMT1500RM2U

(Smart-UPS 1500)

 RBC133
11/2014 (orig. battery put into service)


10/25/2019
 

chaplin + 2 LCDs

sirius + LCD

Serial#: AS1431232892
Manuf. date: July 2014

Rack-mount

BNL tag: A76065

  Control Room,
TPC terminals

APC DLA1500

(SMART-UPS 1500)

 RBC7 11/08/2018

11/20/2021
gmt-ops + LCD

Serial # AS0736230401
Manuf. date: Sept. 2007

Black

BNL tag: A068061

UPS14
(not in RackTables)

Control Room, trigger systems, countertop

 APC SMT1500C

(Smart-UPS 1500)

 RBC7 original factory battery, May 2022

startrg + LCD
 

Serial #: 352208X11667

Manuf. date: February 2022 (bought summer of 2022)

black

IP: 130.199.60.161

BNL tag: A111242

  Contol Room, magnet terminals, behind the LCD for the Windows PC running magnet monitoring

 APC BR1500LCD

(Back-UPS RS 1500)

 RBC109  1/24/2020 rosas + LCD

Serial #: 3B0935X21952
Manuf. date: August 2009

gray/black

*nominally belongs to CAD* possible contacts are John Pomaro or anyone in Collider-Accelerator Support

self-test can be started by holding the power button for *2* beeps (~2-3 seconds)

BNL tag: A83567

  Control Room, under Shift Leader desk APC BR1000G  RBC123 11/30/2017 (though battery was bought in November 2014)

04/12/2023
shift-leader + 2 LCD

Serial #: 3B1204X18994
Manuf. date: January, 2012

black

BNL tag: A132278

PowerChute Personal edition installed on shift-leader system (cannot be used with PowerChute Business Edition)

self-test can be initiated from the front panel by pressing and holding the power button for 6 seconds.  (Caution - pressing and holding the power button for two seconds (one beep) and releasing it will shutdown the UPS!  For the self-test, keep pressing until the 2nd beep!)

             
UPS1  DAQ Room, L4 and server rack (center row, north end) APC SMT1500RM2U
(Smart-UPS 1500)
RBC133 March 2018 (though battery was bought in November 2015)

September 2022
ovirt2

onldb5 (twice, redundant PS)

new servers in 2022 TBC
Serial #: AS1231125008
Manuf. date: July 2012
black, rack mount

bought December 2012
 
 

DAQ Room, on the floor between DB1 and DB2 (the legacy DAQ and trigger racks - southern end of the middle row)

 APC SMT1500

(Smart-UPS 1500)

 RBC7  Original
Battery (3/2011)

February 2015

November 2021
evp3 (bottom PS),

trgscratch (top PS),

sclrscratch (top PS),

daqlocalmain network switch,

daq-sw2 network switch

trgscratch 12 disk external storage array (bottom PS)
 

Serial #: AS1050221151
Manuf. date: Dec. 2010

black

bought March 2011

UPS13 DAQ Room, northeast corner, floor  APC SMT1500C
 
 (Smart UPS 1500)
 RBC7 October 2021 (original factory battery) stargw3.starp.bnl.gov Serial #: 3S2141X15140

Manuf. date: October 2021

black, bought April 2022

IP: 130.199.60.152

BNL tag: A111250
 
UPS2 DAQ Room, rack DB2 (legacy DAQ rack)
 APC SMT2200RM2U

(Smart-UPS 2200)
 
 RBC43  November 2014 (original battery)

November 26, 2019

evp

trgscratch (bottom PS)

sclrscratch (bottom PS)

trgscratch 12 disk external storage array (top PS)

Serial #: AS1431243644
Manuf. date: July 29, 2014

rack-mount
 
UPS15 DAQ Room floor north of shelves in center row  APC SMT2200RM2uC  RBC43 factory original battery (February 2022)

onldb4 (right PS)

onldb3 (right PS)

satabeast1 (right PS)

Serial #:AS2205260230
Manuf. date: Feb. 2022

black

IP: 130.199.50.29

BNL tag: A132277
 

UPS3 DAQ Room DC3

APC SUA1500RM2U

(Smart-UPS 1500)

 RBC24 Oct. 11, 2016

Dec. 6, 2019
barbados2

softioc4

daq-sw1

Serial #: AS0847123095
Manuf. date: Nov. 2008

black, rack-mount

  DAQ Room DC4 APC SMX1500RM2U with

APC SMX48RMBP2U (external battery)
RBC115

2x RBC115
? various SGIS interlock equipment Serial #: AS1039230480

C-AD equipment
UPS4 DAQ Room, rack DB1, bottom APC SMT2200RM2U  RBC43 July 2019

October 2021

l2ana01 (bottom PS)

l2ana02

PCI extension (for l2ana01)

Serial #: AS1336140512
Manuf. date: Sept. 2013
UPS5 DAQ Room, northern Online Linux Pool rack APC SMT2200RM2U RBC43 November 2014 (original battery)

January 23, 2018

June 7, 2019
onl30,

onldb (x2),

mongodev04,

mongodev05,

mongodev06
Serial #: AS1430241567
Manuf. date: July 22, 2014

<DAQ Room Power Panel>
UPS6 DAQ Room, L4 and server rack (DB8, middle row, north end)

APC DLA1500RM2U

(Smart-UPS 1500)

 RBC24  May 27, 2016

 July 9, 2019

 January 2023

 L4 network switch,

 dbbak (both PS)

 dashboard1 (both PS)


 

Serial #: AS0340212578
Manuf. date: Sept. 2003

black, rack-mount

UPS9 DAQ Room middle row shelves APC SMT2200RM2UTW
(Smart-UPS 2200)
RBC43 (Note that the unit itself says it uses an RBC55, if one navigates through the onboard menu.  This appears to be an error on the part of APC). 05/2017
(original battery)


12/2019

January 30, 2023
satabeast3 (left PS)

onldb3.starp (left PS)

onldb4.starp (right PS)
 
Serial #: AS1645262798
Manuf. date: November 2016
UPS10 DAQ Room, middle row shelves (middle shelf) APC SMC1500-2U  RBC132 12/2015 (original battery)

January 28, 2021
stardns1.starp.bnl.gov

24-disk SAS enclosure for  trgscratch and sclrscratch

onldb2.starp (left PS)
Serial #: AS1539124741

Bought December 2015

to initiate self-test: push + hold Mute,then press Display for 2 seconds
  DAQ Room,
bottom of rack "DB9" (center row, north end)
APC SMT2200RM2U  RBC43 5/2017 (original battery, installed at factory 11/2016)

01/2021?

08/2021

06/2022 (disturbingly frequent replacement intervals in this unit...)
cephnfs2 (left PS)

dbbak (top PS)

onlhome (top PS)

stargw2 (in rack DB8)

cephmon01 in rack DB8 (right PS)

cephmon02 in rack DB8 (right PS)

onlpool-s60-01 and onlpool-s60-02 (via a shared extension cord)
Serial #:AS1645260493
Manuf. date: November 3, 2016 (bought May 2017)

2U rack-mount
 
BNL tag: A76075
  DAQ Room, NW corner networking rack

APC SMX2000LV with
2x SMX120BP

 RBC143 October 2020? Various networking equipment

Serial #: AS1913351834

Manuf. date: Mar 2019

rack-mount

*belongs to ITD*

             
UPS16  WAH 1A9 APC SMT1500RM2UC  RBC159 2/2023 (factory original battery)

NPSlaser.starp (Remote power switch for TPC laser PC, though the PC is NOT plugged into it, only a "picomotor multi-axis driver")

Serial #: 3S2205X11933

Manuf. date: Feb. 2022

rack-mount, black

BNL tag: A132276

has a network interface (TBC, and to-be-configured)

   WAH 1B1 APC SMT1500RM2U (Smart-UPS 1500)  RBC133 10/2016 (original battery)

10/2021
tofcontrol

TOF USB hub

Serial #: AS1617143314
Manuf. date: April 2016, bought September 2016

rack-mount, black

  WAH 1C4 APC SMT1500RM2U  RBC133 11/2018 netpower1.starp.bnl.gov (with networking equipment in 1C4) Serial #: AS1243245039
black, 2U rack-mount
Manuf. date: October 2012

bought in January 2013
UPS11 WAH 1C4 APC SMT2200RM2U  RBC43 12/2014 (original battery, installed at factory 8/2014)

November 2021
netpower2.starp.bnl.gov (with networking equipment in 1C4) Serial #:AS1435142781
Manuf. date: July 28, 2014 (bought December 2014)

rack mount

Has overheated and shutdown while in service in the DAQ Room during AC failures (with ambient room temperatures above 90 F (reaching 100 at times)).  So while it seems to be an otherwise reliable unit, it should not be used in an environment where the temperatures may have such uncomfortably high temperatures, nor in the immediate vicinity of other especially warm equipment.
   WAH 2A3

APC SMX1500RM2U

(Smart-UPS 1500)

with external battery pack

 RBC115? unknown gas leak detection systems in 2A2 and possibly C-AD interlock equipment in 2A1

Serial #: AS1039230484
Manuf. date: Sept. 2010

rack-mount, black

battery pack Serial #: QS1002251184
 
*C-AD equipment?*

  WAH 2A9 APC SMT1500RM2U (Smart-UPS 1500)  RBC133 original battery (07/2014)

12/2020

Jan 30, 2023

grant (Wiener/VME) Serial #: AS143611346
Manuf. date: Sept. 2014
black, rack mount
bought March 2015
   WAH 2A9 APC SMT1500RM2U (Smart-UPS 1500)  RBC133 April 2018 TPC interlock distribution panel

surge suppressor with:
-cooling water flow
   meters
-scserv
-2x interlocks 
     equipment in 2A8
Serial #: AS1243245306
Manuf. date: October 2012
black, rack mount
bought ~Dec. 2012
  (in Bldg. 510 when last seen, previously was in the WAH on the floor under the east stairs to RHIC tunnel)

APC BE750G

(Back-UPS ES750)

 RBC17 original battery from ~fall 2010??? nothing when last seen in the WAH (checked 11/20/2015)

Serial #: 5B1039T74854
Manuf. date: Sept. 2010

black

no self-test option

  WAH North Platform, 1st floor west APC SMT1500RM2U (Smart-UPS 1500)  RBC133  01/2019 north-nps1 (and thus all networking equipment on the north platform) Serial #: AS1144220012
Manuf. date: October 2011

rack-mount, black

  AB, near the GMR  PowerWare    fall 2012?
(Batteries likely have been replaced since then under a service contract, handled by STSG)
 gas system equipment  This is a large UPS for circuits in the Gas Mixing Room, under the care of the STSG group.

IP: gmr-ups.starp.bnl.gov
BNL property tag 145850
bought in fall 2012
  AB, mezzanine top floor (northeast corner)  Mitsubishi UP7011A   November 20, 2019 unknown CAD equipment, definitely not STAR's responsibility

labelled "1006 UPS1"

serial port is connected to a Ethernet console server, 130.199.41.64

installed January 2015

Contacts are John Mingoia and Anh Pham

 

This list is maintained as information is made available and is sporadically checked for correctness.  The maintainer of this list is often not informed when STSG adds, removes or replaces UPSes and batteries.  Furthermore, anyone may remove or add equipment to UPSes without informing the maintainer of this list.

 

Spare batteries on hand: 

In a cabinet in the DAQ Room (APC RBC numbers):

7: January 2023 (2 of them)
55: October 2022
109: March 2020
123: to be ordered... April 2023
132: November 2021
133: July 2022
141: October 2020
 
(STSG / electronics techs may have additional spares in the Building 510 labs)